Sizing a CCTV Power Supply: Load, Current and Channel Count

KEY TAKEAWAY

Load = Σ device watts, current = load ÷ voltage, channels ≈ device count. Rate the unit at 1.2–1.3× load, keep a spare channel. Worked example inside.

Two questions stop most people when they size a centralized supply: how much total power do I need, and how many output channels? This article gives a practical method for both, and shows where overloads come from.

1. The basic relationships

Total load P = Σ (wattage of each device)
Total current I = P ÷ supply voltage U
Channels required ≈ number of devices (one device per channel, one fuse per channel)

2. The method

  1. List the rated voltage and the wattage (or current) of every front-end device.
  2. Add up the wattage of devices sharing the same voltage — that gives the load per voltage group.
  3. The sum of the group loads is the total supply power required.
  4. The number of devices gives the channel count; keep one or two channels spare.
  5. Choose a model rated at P × 1.2 to 1.3 or more.

3. Worked example

Twenty DC12V bullet cameras at 2 A each (24 W each).

P = 20 × 24 W = 480 W; I = 480 ÷ 12 = 40 A; 20 channels needed.

Choose a 600 W, 24-channel model such as PS-DC1248-24-2U to keep headroom. A 16-channel unit would not be enough and the specification has to move up to the 24-channel tier.

Note: For long runs, also verify voltage drop — the voltage at the far end has to stay inside the device's operating window. Our online voltage-drop calculator does this.

4. How much headroom

A supply running continuously at full load gets hot and ages faster. As a rule, rate the supply at 1.2–1.3 times the load, and keep one or two channels spare for expansion. How channel count relates to individual device power is covered in How many cameras can one supply feed.

5. Frequently asked questions

Can two devices share one channel?

It is not recommended. Each channel's fuse is sized for one device; putting two on a channel doubles that channel's current, the fuse trips more readily, and one device's failure takes out both.

Can AC24V and DC12V devices be added into the same calculation?

No. Calculate each voltage group separately and select a supply for each — or use a combined supply that provides several voltage groups from one chassis.

Need a model matched to your project?

Send the voltage class, device count and total load — we will confirm the model and the power headroom.

Request a quote